Mechanical pressure switches
S2 type series
S2 type series
Two-stage pressure switches, switching schemes for ZF217
Function-appropriate internal configuration of microswitches I and II, switching scheme selection table. The switch position shown
corresponds to the pressureless state. On the horizontal axis is the switching function of microswitch I (A–D); on the vertical axis is the
switching function of microswitch II (1–4). At the intersection is the switching scheme which satisfies both conditions (e.g. A 2).
Microswitch I (lower switching point)
falling, close
rising, close
falling, open
rising, open
Information required when ordering:
As well as the basic type (e.g. DCM10) and the switching scheme (e.g. A 2), for factory setting it is
also necessary to indicate the switching points and direction of action:
Example: DCM 10-217C-S, switching scheme: A2, Switch I: 6.5 bar falling, Switch II: 7.5 bar rising.
 