32
Mechanical pressure switches
Additonal functions/Connecting schemes
Pressure switches and pressure monitors
Additional functions for Ex-i-equipment
· Housing (500) with terminal connection (IP 65), "blue" cable entry and terminals.
· A lso available with resistor combination for line break and short-circuit monitoring (with isolating amplifier).
! Important:
All pressure switches with the ZF5… additional functions listed here can only be operated in combination with
a suitable isolating amplifier.
DWAM6-576
i Additional information:
Our pressure switches and thermostats are considered to be "simple electrical equipment" within the meaning
of standard EN60079-11: 2007. Testing is not mandatory for this type of equipment.
i ATEX-Certificate: please see page 10 – 13
Additional functions for Ex-ia-equipment
Connection scheme
II 1/2G Ex ia IIC T6 Ga/Gb
II 1/2D Ex ia IIIC T80 °C
Gold-plated contact
ZF513
single pole switching, fixed hysteresis,
not adjustable
Switching capacity:
max. 24 VDC, 100 mA, min. 5 VDC, 2 mA
For the power supply circuit:
Ui 24 V DC
Ii 100 mA
Ci 1 nF
Li 100 µH
Versions with resistor combination for line break and short-circuit monitoring in control current circuit, see DBS series,
pages 54 – 56:
For the power supply circuit:
Ui 14 V DC
Ri 1500 Ohm
Ci 1 nF
Li 100 µH
Normally closed contact with resistor
combination, for minimum pressure
monitoring, gold-plated contact,
plastic-coated housing (chemical version).
ZF574
Normally closed contact with reclosing
lockout and resistor combination,
for minimum pressure monitoring,
plastic-coated housing (chemical version).
ZF575
see
DBS series
pages 54 – 56
Normally closed contact with resistor
ZF576
combination, for maximum pressure
monitoring, gold-plated contact,
plastic-coated housing (chemical version).
Normally closed contact with reclosing
ZF577
lockout and resistor combination,
for maximum pressure monitoring,
plastic-coated housing (chemical version).
 