DatasheetQ Logo
Electronic component search and free download site.
Transistors,MosFET ,Diode,Integrated circuits

E53-CNBN2 View Datasheet(PDF) - OMRON Corporation

Part Name
Description
Manufacturer
E53-CNBN2
Omron
OMRON Corporation Omron
E53-CNBN2 Datasheet PDF : 13 Pages
1 2 3 4 5 6 7 8 9 10 Next Last
E5CN-H
External Connections
A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
Controllers
Control output 1
 Relay output
250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear voltage output
0 to 10 VAC
Load 1 kΩ min.
Current output
0 to 20 mA DC
4 to 20 mA DC
Load 600 Ω max.
The Temperature Controller is set for a K-type
thermocouple (input type = 5) by default. An input error
(s.err) will occur if the input type setting does not agree
with the temperature sensor. Check the input type.
1
Control output 1
2
DO NOT DO NOT A
USE
USE
3
mA
B4
V
DO NOT
USE
B5
Auxiliary outputs Auxiliary outputs (relay outputs)
(relay outputs) 250 VAC, 3 A
11
6
(resistive load)
Auxiliary output 2
12
7
A heater burnout alarm, SSR
Auxiliary output 1
failure, heater overcurrent alarm,
13
8
?
or input alarm is sent to the
output to which the alarm 1
14
9
function is assigned.
15
10
Input power supply
100 to 240 VAC
24 VAC/VDC (no polarity)
Option Units
E53-CNBN2
Event Inputs
E53-CNQBN2
Event Inputs and
Control Output 2
11
EV1 12
EV2
13
DO NOT 14
USE
DO NOT 15
USE
11
EV1 12
EV2
13
Control output 2 14
12 VDC 21 mA 15
E53-CNHBN2
Event Inputs
and CT
E53-CNBFN2
Event Inputs and
Transfer Output
11
EV1 12
EV2
13
14
CT1
15
11
EV1 12
EV2
13
14
Transfer output
15
4 to 20 mA DC
(Load 600 Ω max.)
E53-CNQHHN2
Control Output 2
and CT2
E53-CNQFN2
Control Output 2 and
Transfer Output
Control output 2 11
12 VDC 21 mA
12
13
CT2
14
CT1
15
Control output 2 11
12 VDC 21 mA
12
DO NOT
USE
13
14
Transfer output
15
4 to 20 mA DC
(Load 600 Ω
max.)
E53-CN01N2
Communications
(RS-232)
RS-232C
SD 11
RD 12
SG 13
DO NOT
USE
14
DO NOT
USE
15
E53-CNH01N2
Communications
(RS-232) and CT
RS-232C
SD 11
RD 12
SG 13
14
CT1
15
E53-CNQ01N2
Communications (RS-232)
and Control Output 2
RS-232C
SD 11
RD 12
SG 13
Control output 2 14
12 VDC 21 mA
15
E53-CN03N2
Communications
(RS-485)
E53-CNQ03N2
Communications (RS-485)
and Control Output 2
E53-CNH03N2
Communications
(RS-485) and CT
E53-CNHH03N2
Communications
(RS-485) and CT2
E53-CNQHN2
Control Output 2
and CT
B (+) 11
RS-485
A () 12
DO NOT
USE
13
DO NOT
USE
14
DO NOT
USE
15
B (+) 11
RS-485
A () 12
DO NOT
USE
13
Control output 2 14
12 VDC 21 mA
15
B (+) 11
RS-485
A () 12
DO NOT
USE
13
14
CT1
15
B (+) 11
RS-485
A () 12
13
CT2
14
CT1
15
Control output 2 11
12 VDC 21 mA
12
DO NOT
USE
13
14
CT1
15
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
9
 

Share Link: 