DatasheetQ Logo
Electronic component search and free download site.
Transistors,MosFET ,Diode,Integrated circuits

E53-CNPBN2 View Datasheet(PDF) - OMRON Corporation

Part Name
Description
Manufacturer
E53-CNPBN2
Omron
OMRON Corporation Omron
E53-CNPBN2 Datasheet PDF : 15 Pages
First Prev 11 12 13 14 15
E5CN/E5CN-U
External Connections
A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. (If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.)
Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.
E5CN
Controllers
Control output 1
Long-life relay output
250 VAC, 3 A (resistive load)
Relay output
250 VAC, 3 A (resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
Current output
0 to 20 mA DC
4 to 20 mA DC
Load: 600 Ω max.
Control output 2
Voltage output (for driving SSR)
12 VDC, 21 mA
Option Units
The E5@N-@@@T@ is set for a K-type
thermocouple (input type = 5) by default. An
input error (s.err) will occur if the input type
setting does not agree with the temperature
sensor. Check the input type.
Control output 1
DO NOT DO NOT A
mA USE
USE
B
V
DO NOT
USE
Analog input
B
TC/Pt
universal input
Auxiliary outputs (relay outputs)
250 VAC, 3 A
(resistive load)
Auxiliary outputs
(relay outputs)
Auxiliary output 2
Auxiliary output 1
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
A heater burnout alarm, heater short alarm,
heater overcurrent alarm, or input alarm is
sent to the output to which the alarm 1
function is assigned.
E53-CNHH03N2
Communications
(RS-485) and CT2
B(+) 11
RS-485
A() 12
13
CT2
14
CT1
15
E53-CNHBN2
Event inputs
and CT
11
EV1 12
EV2
13
14
CT1
15
E53-CNQ03N2
Communications
(RS-485) and
Control Output 2
B(+) 11
RS-485
A() 12
DO NOT 13
USE
+ 14
Control output 2
15
E53-CNPBN2
Event Inputs and
External Power Supply
E53-CNPHN2
External Power
Supply and CT
11
EV1 12
EV2
13
External +
14 12 VDC,
power supply
20 mA
15
External +
power supply
11 12 VDC,
20 mA
12
DO NOT 13
USE
14
CT1
15
E53-CNP03N2
Communications (RS-485)
and External Power Supply
B(+)
11
RS-485
A() 12
DO NOT 13
USE
External+
power supply
14
12 VDC,
15 20 mA
E53-CNH03N2
Communications
(RS-485) and CT
B(+) 11
RS-485
A() 12
DO NOT 13
USE
14
CT1
15
E53-CN03N2
Communications
(RS-485)
B(+)
11
RS-485
A() 12
DO NOT 13
USE
DO NOT 14
USE
DO NOT 15
USE
E53-CNBN2
Event inputs
11
EV1 12
EV2
13
DO NOT 14
USE
DO NOT 15
USE
E53-CNQHN2
Control Output 2
and CT
+ 11
Control output 2
12
DO NOT 13
USE
14
CT1
15
E53-CNQHHN2
Control Output 2
and CT2
+ 11
Control output 2
12
13
CT2
14
CT1
15
E53-CNQBN2
Event Inputs and
Control Output 2
11
EV1 12
EV2 13
+ 14
Control output 2
15
E5CN-U
The E5@N-@@@T@ is set for a
K-type thermocouple (input type = 5)
by default. An input error (s.err) will
occur if the input type setting does
not agree with the temperature
sensor. Check the input type.
Control output 1
Relay output
(three terminals used)
SPDT, 250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Current output
4 to 20 mA DC
0 to 20 mA DC
Load: 600 W max.
DO NOT
USE
mA
V
DO NOT
USE
Analog input
Control output 1
DO NOT A
USE
B
B
TC/Pt
universal input
Note: For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately.
Auxiliary output
250 VAC, 3 A (resistive load)
(Relay outputs)
Auxiliary output 1
Auxiliary output 2
(Control output (cooling side))
Input power supply
An input error is sent to the
output to which the alarm 1
function is assigned.
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
11
 

Share Link: 