E5AX-P
E5AX-P
Specifications
Ratings
Supply voltage
Operating voltage range
Power consumption
Input
Potentiometer input
Control output
Control mode
Alarm output
Setting method
Indication method
Other functions
100 to 240 VAC, 50/60 Hz (either frequency applicable with same unit)
85% to 110% of rated supply voltage
Approx. 10 VA (at 100 VAC) to 15 VA (at 240 VAC)
Approx. 12 VA (at 100 VAC) to 15 VA (at 240 VAC) with communication function
Thermocouple (K/J/T/E/R/S/L/U) or platinum resistance thermometer (Pt100/JPt100)
selectable
100 W to 2.5 kW
Relay output: open, close; SPST-NO contacts; 3 A, 250 VAC (resistive load); inrush current: 1
A max.
PID control with auto-tuning
Relay output, SPST-NO contacts; 3 A, 250 VAC (resistive load)
Digital setting via Up and Down Keys
Digital indications (character heights PV: 15 mm and SV: 11 mm) (Color PV: red, SV: green)
Upper and lower limits for set value
Key protection
Input shift
Display unit selection (%C/%F)
Normal and reverse output selection
Valve position display
Motor calibration function
Watchdog timer function (Detects failures in the CPU and restores the CPU.)
Manual output (balanceless-bumpless operation switchable)
Communications
Protocol
Transmission method
Synchronization method
Baud rate
Transmission code
Communications Write to
Temperature
Controller
Read from
Temperature
Controller
RS-232C, RS-422, RS-485
BCD
Transmission output
Half-duplex
Data select code
4 to 20 mA DC
Load: 600 W max.
Resolution: Approx. 3,200
Start-stop synchronization
---
---
150/300/600/1,200/2,400/4,800/9,600 bps
ASCII (7-bit)
Main setting, set alarm value, proportional Main setting, set
band, integral time, derivative time, AT
alarm value
start/stop etc.
Write disabled
Main setting, set alarm value, proportional
band, integral time, derivative time, set
limit value, process value, valve position,
error codes, etc.
Main setting, set
alarm value,
process value, error
codes, etc.
Process value (see note 3),
valve position
Note: 1. The maximum total cable length must not exceed the following limits.
RS-422: 500 m; RS-232C: 15 m; RS-485: 500 m
2. A maximum of 32 Temperature Controllers can be connected to one host computer using serial communications (RS-422, RS-485).
3. Outputs the temperature data within the set limits.